Sending The Ground Rod to Earth.
Bonding is the “permanent joining of
metallic parts to form an electrically conductive path that ensures electrical
continuity and the capacity to conduct safely any current likely to be
imposed.”
All Metallic structures in a facility that can be
energized due to an earth or ground fault, static electricity buildup or
lightning strikes are bonded together then connected to the electrical system
earth point. This practice is called Equi-Potential Bonding.
In some installations, the bonding loop for lightning
protection is separate from the bonding loop for electric motors, cable trays,
metallic pipes, and steel structures.
The electrical system earth point is the point where
the grounding wires are physically connected to the earth with the aid of a
grounding electrode.
The grounding electrode generally stabilizes voltages from the power source as in the case where the neutral of a transformer is bolted to ground and
driven into the earth. the grounding electrode is also used to dissipate
a static discharge to earth and provide a return path for AC current to go back to its source
Sending the ground rod into the earth
is not just as simple as pounding a rod into the soil. there are guidelines for
proper grounding. because a poorly grounded system is just as dangerous as no
grounding at all.
Common grounding guidelines and their
reason
Length of Ground rod
NEC and UL require that Ground rods shall not be less than 5/8 inch in diameter
by 8 feet in length. It all depends on the resistance of your soil the 8ft rod
ensures that most parts of the rod are in contact with the surrounding earth and there is
good continuity between the rod and the earth. The resistivity of the topsoil is
always higher than the resistivity of the deeper layers of the soil so a long
rod goes deeper into the earth's crust where soil resistance is lower and more
stable thereby offering better grounding. You could measure the resistance if
the earth using ground resistance tester.
Soil Resistance
NEC 250.56 requires that the system impedance to ground is less than 25 ohms. However, the NFPA and IEEE recommend a ground resistance value of 5 ohms or less. Ideally, the ground should have no resistance at all, that is the
ground should be of zero ohms resistance but in practice, there is always some resistance.
To achieve an
acceptable ground resistance value, the soil could be treated with a salt such as copper
sulfate, magnesium sulfate, or sodium chloride and water. Over time the salts
leach into the soil to reduce earth resistivity. Cow dung is used in some
cases to treat the soil because they retain higher moisture levels and
have a higher electrolyte level. However, in some countries, local environmental regulatory bodies
object to adding salt or heaps of cow dung to the soil.
Ground rod spacing.
If ground
resistance measurements are taken and the earth resistance is well above the
minimum acceptable value a second rod could be driven into the ground and NEC
requires that you space the rods at least 6 ft apart. To simplify this, the distance between the rods should be equal to or
a bit more than the length of the rod. Ground rods spaced less than two
rod-lengths apart will interfere with each other. In other words, their spheres of influence will intersect and the resistance will not be lowered.
Comments
Post a Comment