Current Transformer: Basics
A current transformer is a type of
instrument transformer used to step down large values of current on the primary
side to a manageable level of secondary current proportional to the amount of
current flowing through the primary.
When
you see a CT with 800:5 ratio, it means the circuit is operating in the range
of 0 to 800 Amps on the primary side and it would step the current down
proportionally to the range 0 to 5 Amps for the devices on the secondary side.
The output from the secondary side of a current transformer is usually used for operating measuring devices like
ammeters and protective devices like relays. The current transformer provides
electrical isolation for the measurement and protective devices on the
secondary side as these
devices are insulated away from the high-voltage and current on the primary
side.
Working Principle
The working principle of the current transformer is the same as that of the voltage transformer it contains a primary and a secondary
winding. Whenever an alternating current flows through the primary winding, an
alternating magnetic flux is produced, which then induces an alternating current
in the secondary winding but unlike the voltage
or power transformer, the current transformer consists of only one or very few
turns as its primary winding. The primary winding could be just a conductor placed
through a hole on the current transformer and the secondary winding consists of copper
coils wrapped around an iron core
The current transformer in its most basic form is
just an inductor placed around a current-carrying conductor. The inductor is used to sense the magnetic field caused
by the changing current flowing
through the conductor. Just like in the image below.
Although
in actual construction, an iron core is used to confine the magnetic flux
generated by the current-carrying conductor so that much of it gets to the
secondary coil and induce current in the secondary coil. A more accurate
representation of the current transformer would be the image below.
Most
current transformers have a standard secondary rating of 5 amps or 1 amp.
Current flows on the secondary side of a CT only if the secondary circuit is closed or
connected to a load. In fact the secondary side of a current transformer should
never be left open because as we know:
In
essence the voltage ratio is opposite to the current ratio. As the CT steps down current, also steps
up voltage and for this reason, extremely high voltages would be induced at the terminals
of the CT which could pose a risk of electrocution to human and a risk of damaging the CT due to insulation failure caused by high voltages stresses.
An in-depth explanation of why the secondary side of a CT should never be left open is that the current flowing in the primary side produces a magnetic flux on
the core of the current transformer and the current flowing on the secondary
side produces a counter magnetic flux. When the secondary is open, there will
be no secondary current flowing, and no counter magnetic flux will be produced.
Due to the absence of a counter-magnetic flux, a very high flux is set up in
the core of the transformer. The high flux leads to core overheating due to
excessive core losses. It also causes very high voltages to be induced across
the terminals on the secondary side.
For
this reason the secondary of a current transformer should always be shorted if
it is not connected to a load. When it is shorted voltage becomes zero and the
maximum current flows but we all and we know that the current is low in most cases, 5A or
1A.
Types Of Current
Transformer
Window or Ring Type
Current Transformer.
These
are the most commonly used type of current transformers. They do not contain a
primary winding. Instead, the current-carrying conductor is threaded through the window
or hole in the current transformer and thus conductor becomes the primary
winding in the setup. Some of them have a “split core” which allows them to be
opened, installed, and closed, without disconnecting the circuit to which they
are attached to.
Bar Type Current
Transformer
These type of current transformers are usually bolted to the
current-carrying conductor. In most cases, the conductor is a bus bar and the transformer is
installed on the bus bar to measure the amount of current the bus bar is
carrying.
Wound Type Current
Transformer.
This current transformer is referred to as wound type because of its
construction. The primary winding is wound on the same core as the secondary winding. The primary winding is wound on the top of the
secondary winding and a suitable insulating material is used to separate the
two windings. Typically, they are used in applications that require small current
transformation ratios. Also, they are more accurate and they have a higher
burden capacity.
Modifying the turns ratio.
The CT ratio is the ratio of primary current input to secondary current
output at full load. Most current transformers have a standard secondary
rating of 5 amps with the primary and secondary currents being expressed as a
ratio such as 75:5, 100:5, 150:5, 300:5 and so on and so forth.
Let’s take 300:5 as an example.
This current transformer will produce 5 amps at the secondary when 300 amps
flow through the primary. In other words, the primary current is scaled down by
60.
This is so because, in a current transformer, rated primary amperage
divided by the rated secondary amperage is proportional to the turns ratio of the current
transformer. We can see that 300 ÷ 5 equals 60 or 60:1. Meaning 60 turns in the secondary to 1 turn in the
primary.
So if we double the turn in the primary it becomes 60:2 or, similarly if
we triple the turn in the primary it becomes 60:3.
The rated secondary amperage (Is) of the current transformer is fixed at
5A and cannot be modified so when we increase the primary turns we have to
figure out what the new rated primary amperage (Ip) would be. This can be achieved
using the following formula.
Where: Ip = Rated primary
amperage of CT
Is = Rated
Secondary Amperage of CT
Ns = Number of
secondary turn
Np = Number of
Primary turn
Calculating our new Rated Primary amperage (Ip) for 2 turns we can say
Ip x Np = Is x Ns
Ip x 2 = 5 x 60
Ip x 2 = 300
Ip = 300/2
Ip = 150A
Similarly to find the new Rated Primary amperage (Ip) for 3 turns
Ip x Np = Is x Ns
Ip x 3 = 5 x 60
Ip x 3 = 300
Ip = 300/3
Ip = 100A
Comments
Post a Comment