Fundamental's of Contact resistance testing

 


Contact resisting test is a kind or commissioning, or maintenance test done to measure the resistance of an electrical connection. The connection could be pressed together, bolted, soldered, clamped or welded. Contact theory assumes that at some scale the metal surfaces are never completely flat.

The main purpose is to confirm the integrity of an electrical connection and catch problems very early if one exists. The Contact Resistance measurement 
can detect the following problems loose connections, bolted joints that are not adequately tensioned, corroded contacts surfaces and eroded/pitted contact surfaces. 

This test is usually carried out on, circuit breakers, contactors, relays and switches in closed condition to verify that the contacts make properly and there would be no heating on load. It is also carried out on cable terminations, joints, and busbar sections for the same reason listed above.

In the case of circuit breakers and fused contactors, they experience mechanical wear and tear on their contacts due to the arc that develops on opening and closing of the contacts during breaker operation.  The integrity of the contacts in vacuum bottles cannot determined as they are encased inside the bottle but even if they were visible like those of an Air Circuit Breaker the eye is not a good gauge to ascertain the integrity of the contacts. 

Contact resistance measurement is a perfect for proactive maintenance and to prevent a catastrophic failure.

ACCEPTABLE LIMIT FOR LOW RESISRTANCE TESTING

A low resistance test is a measurement where the typical values expected is below 1ohm. Values as low as 0.1 micro-ohm could be read from some low resistance testers which is why we don't use normal multimeters for contact resistance testing.

 A maximum contact resistance of 20 micro-ohms is usually quoted as the acceptable limit for a good electrical contact point.  For example, if you are testing a MV circuit breaker from stab to stab you should be aware that there is more than one contact point, the stab is bolted to the circuit breaker, the movable contact is usually also bolted in so if you evaluate carefully there could be more than 4 electrical connections/contacts. In this situation, the minimum resistance you should accept is 80 micro-ohms.



HOW IT WORKS AND PROCEDURE

Our test is carried out using a Megger digital low resistance micro-ohmmeter. (DLRO10). It works using the four-wire (Kelvin Bridge) DC voltage drop method.

This method involves connecting two pairs of wires to the material under test:

  • The wires are C1,C2, P1 &P2
  • The Current wires (C1 and C2) carry the current (I) to the test piece.
  • The Voltage wires (P1 and P2) measure the potential difference (V) across the test piece.
  •  A known current (I) is passed through the current wires (C1 and C2).
  • The voltage drop (V) across the device or material is measured using the voltage wires (P1 and P2).
  • The tester knows how much current it injected into the test piece,
  • From Ohm’s Law, if we pass a current through a resistance we will generate a voltage across the resistance.  The voltage developed between the two points where the probes touch the test item is measured by the tester and the resistance (R) is calculated by the tester using Ohm's law: R = V/I.


 


Comments

Popular posts from this blog

How to check continuity over long distance

Making sense of a transformer nameplate data

Stall Rotor Protection Using Magnetic Overload Relays Oil Dashpot type