Fundamental's of Contact resistance testing
Contact resisting test is a
kind or commissioning, or maintenance test done to measure the resistance of an
electrical connection. The connection could be pressed together, bolted, soldered, clamped or welded.
Contact theory assumes that at some scale the metal surfaces are never
completely flat.
The main purpose is to confirm the integrity of an electrical connection and
catch problems very early if one exists. The Contact Resistance measurement can detect the following problems loose
connections, bolted joints that are not adequately tensioned, corroded
contacts surfaces and eroded/pitted contact surfaces.
This test is usually carried out on, circuit breakers,
contactors, relays and switches in closed condition to verify that the contacts
make properly and there would be no heating on load. It is also carried out on
cable terminations, joints, and busbar sections for the same reason listed
above.
In the case of circuit breakers and fused contactors, they experience mechanical wear and tear on their contacts due to the arc that develops on opening and closing of the contacts during breaker operation. The integrity of the contacts in vacuum bottles cannot determined as they are encased inside the bottle but even if they were visible like those of an Air Circuit Breaker the eye is not a good gauge to ascertain the integrity of the contacts.
Contact resistance measurement is a perfect for proactive maintenance and to prevent a catastrophic failure.
ACCEPTABLE LIMIT FOR LOW RESISRTANCE TESTING
A low resistance test is a measurement where the typical values
expected is below 1ohm. Values as low as 0.1 micro-ohm could be read
from some low resistance testers which is why we don't use normal multimeters
for contact resistance testing.
A maximum contact
resistance of 20 micro-ohms is usually quoted as the
acceptable limit for a good electrical contact point. For example, if you
are testing a MV circuit breaker from stab to stab you should be aware that
there is more than one contact point, the stab is bolted to the circuit
breaker, the movable contact is usually also bolted in so if you evaluate
carefully there could be more than 4 electrical connections/contacts. In this
situation, the minimum resistance you should accept is 80 micro-ohms.
HOW IT WORKS AND PROCEDURE
Our test is carried out using a Megger digital low resistance
micro-ohmmeter. (DLRO10). It works using the four-wire (Kelvin
Bridge) DC voltage drop method.
This method involves connecting two pairs of wires to the
material under test:
- The wires are C1,C2,
P1 &P2
- The Current wires
(C1 and C2) carry the current (I) to the test piece.
- The Voltage wires
(P1 and P2) measure the potential difference (V) across the test piece.
- A known
current (I) is passed through the current wires (C1 and C2).
- The voltage drop
(V) across the device or material is measured using the voltage wires (P1 and P2).
- The tester knows how much current it injected into the test piece,
- From Ohm’s Law, if we pass a current through a resistance we will generate a voltage across the resistance. The voltage developed between the two points where the probes touch the test item is measured by the tester and the resistance (R) is calculated by the tester using Ohm's law: R = V/I.
Comments
Post a Comment